Duplicated degrees-of-freedom component exist at the Rigid Link (Diaphragm) of Node no. 3565.
Question:
please see the attached model
please see the attached model
Answer:
Hello,
Those error is because of duplication of Rigid link and diaphragm. Rigid link cannot be duplicated with the diaphragm, so please change the "consider --> do not consider" in Floor diaphragm via structure > building > Control data > Story data.
Or if you want to consider the Floor diaphragm, use elastic link instead of rigid link.
Thank you.
Best regards,
Jihong Hwang
Those error is because of duplication of Rigid link and diaphragm. Rigid link cannot be duplicated with the diaphragm, so please change the "consider --> do not consider" in Floor diaphragm via structure > building > Control data > Story data.
Or if you want to consider the Floor diaphragm, use elastic link instead of rigid link.
Thank you.
Best regards,
Jihong Hwang