Shear Connectors

Question:

Please help,

I have defined parameters for all composite beams. However, after I run the design. No shear connector is checked. Please let me know if I missed any step. Thanks.

Ken




Answer:

Hello,

Kindly send us the model file for review.

Regards,
Nandeep
Technical Manager, MIDAS

Here is the file. Please advise. Thanks.





Hello,

Sorry I couldn't write back earlier.
Actually the Fatigue 1 and 2 load combinations were not selected and hence the shear connectors weren't being checked.  Kindly classify these combinations and the connectors would be checked.
Kindly let us know if further assistance would be required.

Regards,
Nandeep
Technical Manager, MIDAS